Apartment Handover in Bengaluru
This is a real HomeGyan inspection report, published with the homeowner's privacy protected. Every finding, photograph and measurement is exactly as recorded on site. Only the identifying details β owner name, unit number, project name, builder and street address β have been replaced.
Apartment Handover in Bengaluru
123 Β· Bengaluru
New Apartment Handover Inspection
Walls and quadrants are numbered the same way in every room, so a defect can be found again from the report alone β including by a contractor who was not present at the inspection.
Moisture meters report a WME (wood moisture equivalent) percentage. On concrete, plaster and drywall that figure is not an absolute water content β it is read on a relative scale to judge whether a surface is dry, at risk, or actively wet.
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Main door frame alignment and closing | Recommended to fix | Main door frame slightly missaligned. Crack between door frame and wall - Need better caulking or sealing. |
Main door lock | OK | β |
Door viewer, calling bell and intercom | Monitor | Door Viewer not installed. Only hole provided. Calling bell and intercom not inspected. |
Foyer flooring, skirting and niche finish | Monitor | Hollowness observed at the below places: Attn: R - Row , C - Column R4C2 = Row 4 and Column 2. R4 C2 R6 4C R10 C1 R11 C5 R12 C1 Crack observed at R4 C3 |
Living room wall and paint finish | Recommended to fix | Uneven paint finishing at the corner of the balcony and living room - The right corner. See attached image. |
Living room wall plumb and squareness | OK | Visual inspection looked okay. |
Wall plaster flatness | OK | β |
Living/dining flooring level and joints | OK | β |
Skirting alignment and floor junction | OK | β |
False ceiling and edge finishing | OK | False ceiling not installed. So, not inspected |
Ceiling soffit cracks and patch marks | OK | β |
Living area switchboards and socket points | Monitor | The electrical light point above the switchboard, which is attached to the balcony wall is not working. |
TV, internet and AC point provision | OK | Visual inspection looked okay. Points provided and checked. |
Light points, [redacted] lighting and fan hook | OK | Not applicable. Visually inspected - No lights were installed. |
Living/dining window glazing and seal | Recommended to fix | The balcony door has an uneven finish from the outside. The window close to main door has a screw cap is missing from the frame. |
Curtain rod blocking above windows | OK | Not provided/inspected |
Dining wash basin, tap and drain | OK | Not provided |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Kitchen counter level and slope | Monitor | Kitchen counter not provided. |
Counter slab joints, edge polish and overhang | Monitor | Kitchen counter/slab not provided. |
Cabinet shutter alignment and hinges | OK | Not yet installed |
Cabinet internals, drawers and channels | OK | Not yet installed |
Sink trap and under-sink leakage | OK | Not yet installed |
Sink bowl fixing and drain board slope | OK | Not yet installed |
Hot and cold inlet points with angle valves | OK | β |
Dado tiling and sealant quality | Monitor | Dado tile yet to be installed |
Gas pipeline / PNG-LPG point safety | Monitor | Gas connection not provided |
Chimney duct, exhaust outlet and hob cutout | OK | Not yet installed |
Kitchen power points and RCD protection | OK | Inspected - all okay |
Water purifier point and drain | OK | Visually inspected - Point provided. Not installed. |
Kitchen floor level | OK | β |
Kitchen window, mesh and ventilation | Monitor | Mosquito mess not installed. Provision to install is available. |
Loft slab, shutters and access | OK | Not inspected |
Fittings brand/model matches builder specification | OK | Not inspected - no fittings installed yet. Builder specification not provided. |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Utility area plumbing/electrical points | OK | Checked plumbing and electrical points within kitchen. Everything looked okay. |
Washing machine inlet, drain and power | OK | Provision provided - All electrical work looks good. |
Utility floor slope to drain | OK | Not applicable. |
Utility sink, tap and waste connection | OK | Addressed within kitchen area. |
Water inlet line, meter and shutoff | OK | Not applicable |
LPG cylinder space and ventilation | OK | Not applicable as utility section is not available. |
Cloth drying provision | OK | Not applicable as utility section is not available. |
Utility door, mesh shutter and lock | OK | Not applicable as utility section is not available. |
Utility waterproofing and adjoining wall | OK | Not applicable as utility section is not available. |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Wall surface and paint finish | Monitor | Minor crack found in Wall one - the wall with the door is wall one. The crack is touched up with paint, looks like a cosmetic issue not structural. Check with builder once. |
Flooring finish and skirting line | Monitor | Wall skirting needs to have a better finish. Better caulking or sealing needed. |
Skirting gaps and corner mitres | OK | β |
Ceiling and cornice finish | OK | β |
Wardrobe shutters and internal fitment | OK | Not applicable |
Wardrobe shelves, drawers and hanging rod | OK | Not applicable |
Window operation and weather seal | OK | β |
Window grill / safety mesh | Monitor | Window grill/safety mesh not installed. Mosquito net provision provided, but not installed. |
Switchboards, sockets and AC point | OK | β |
AC sleeve, drain slope and outdoor unit space | OK | β |
TV, telephone and data points | OK | β |
Bedroom door, latch and privacy lock | Monitor | Master bedroom handle door not auto locking |
Attached bathroom door and water barrier | OK | β |
Balcony door, threshold and water stop | OK | Not Applicable |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Wall and ceiling paint finish | Monitor | Wall crack observed at corner of wardrobe area. Right above the hollow tile. This looks cosmetic. But good to check with builder once. |
Floor level, joints and skirting | Monitor | 1. Hollowness observed at R4 C3 2. Uneven tile observed at R1C1, R2C1 3. Tile chip-off observed at R6C5 |
Ceiling finish and false ceiling edges | OK | Ceiling checked, False ceiling not applicable. |
Door shutter, latch and stopper | Recommended to fix | 1. Uneven gap observed between door and door frame 2. Handle auto lock not working. |
Window shutters, mesh and latch | Monitor | 1. Mosquito mess provision available but not provided. 2. Screw cap not provided for window frame |
Window grill / safety mesh | Monitor | Window grill not provided |
Wardrobe provision and fitment | OK | Not Applicable |
Power points and light fixtures | OK | β |
AC point, sleeve and drain | OK | β |
TV and data points | OK | β |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Wall and ceiling paint finish | OK | No issues observed |
Floor level, joints and skirting | Recommended to fix | Scratches observed at multiple tiles: R1C3, R1C4, R1C5, R2C4, R3C6, R4C1, R4C6 |
Ceiling finish and false ceiling edges | Monitor | Uneven cement work in the outside ceiling finish. |
Door shutter, latch and stopper | Recommended to fix | Handle auto lock not working. |
Window shutters, mesh and latch | Monitor | Mosquito net provision available but not installed/provided |
Window grill / safety mesh | Monitor | Window grill not provided |
Wardrobe provision and fitment | OK | Not applicable as wardrobe not installed. |
Power points and light fixtures | OK | β |
AC point, sleeve and drain | OK | β |
TV and data points | OK | β |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Floor slope towards drain | Recommended to fix | Faulty Drainage in common bathroom. The slope needs to be checked for proper drainage. |
Floor trap, grating and drainage speed | Recommended to fix | Slow drainage - needs checking. Hollowness observed at the floor tile near drain |
Wall tile alignment and grouting | Recommended to fix | Wall 1 - The entry wall -One with the door Wall 2 - The Left wall Wall 3 - The wall opposite to entry wall Wall 4 - The right wall. Quadrant 1 is the right top of the wall Quadrant 2 is the right bottom of the wall Quadrant 3 is the left bottom of the wall Quadrant 4. is the left top o 1. Hollowness observed at Wall 4 - (Quadrant 3 tiles) f the wall 2. Uneven tile observed at Wall 4 quadrant 3 3. Dado tile chip-off observed at Wall 2 quadrant 3 |
Tile joint width, grout and cut placement | OK | β |
Taps, mixers and shower leakage | Monitor | Tap not provided yet in the common bathroom |
CP fittings brand/model match specification | OK | β |
Health faucet, angle valve and fixing | OK | β |
WC fixing, seat and flush operation | OK | β |
Wash basin, counter, waste and trap | OK | β |
Sanitaryware free from chips, cracks and stains | OK | β |
Under-counter basin support and fixing | OK | β |
Bottle trap, angle cock and connection hoses | OK | β |
Shower zone slope, ledge and partition | OK | β |
Exhaust fan and geyser point | OK | β |
Geyser dedicated MCB and clearance | OK | β |
Exhaust duct termination and shaft | OK | β |
Water pressure and flow at all outlets | OK | Water pressure as per standard specifications - between 1.5 to 5. Observed 3 kg/cm2 |
Mirror, shelf and accessory fixing | OK | Not applicable |
Bathroom door, threshold and lock | OK | β |
Concealed plumbing access panel | OK | β |
Signs of waterproofing failure | OK | β |
Bathroom False Ceiling | Monitor | False Ceiling channel needs to be fixed properly |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Floor slope towards drain | Monitor | Water storage observed near drainage. Needs a better sloping. |
Floor trap, grating and drainage speed | OK | β |
Wall tile alignment and grouting | Monitor | 1. Hollowness observed at the tile near drain. 2. Hollowness observed at dado tile wall 1 quadrant 4 3. Hollowness observed at dado tile wall 3 quadrant 2 |
Tile joint width, grout and cut placement | OK | β |
Taps, mixers and shower leakage | Monitor | Tap not provided |
CP fittings brand/model match specification | OK | β |
Health faucet, angle valve and fixing | OK | β |
WC fixing, seat and flush operation | OK | β |
Wash basin, counter, waste and trap | OK | β |
Sanitaryware free from chips, cracks and stains | OK | β |
Under-counter basin support and fixing | OK | β |
Bottle trap, angle cock and connection hoses | OK | β |
Shower zone slope, ledge and partition | Monitor | Slope drainage slow. Needs checking! |
Exhaust fan and geyser point | OK | β |
Geyser dedicated MCB and clearance | OK | β |
Exhaust duct termination and shaft | OK | β |
Water pressure and flow at all outlets | OK | β |
Mirror, shelf and accessory fixing | OK | β |
Bathroom door, threshold and lock | Monitor | Gap between door frame and the wall need to be filled properly |
Concealed plumbing access panel | OK | β |
Signs of waterproofing failure | OK | β |
Bathroom False Ceiling | Recommended to fix | False Ceiling channel needs to be fixed. |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Balcony floor slope and drain outlet | Monitor | Water drainage not working as expected. Water logging see close to railings wall. |
Balcony floor tile and anti-skid finish | OK | β |
Railing fixing and height | OK | β |
Railing height and baluster gap | OK | β |
Glass railing marking and fixing | OK | β |
Balcony door threshold and water stop | OK | β |
Balcony soffit, drip mould and paint | OK | β |
Parapet wall finish and coping | OK | β |
Balcony light point and weatherproofing | OK | β |
Seepage into the adjoining room | OK | β |
Balcony floor tile | Monitor | 1. Crack tile found near drain outlet. The tile is attached to the railing wall 2. Hollowness observed at balcony R4C3 3. Uneven tile observed at balcony R9C2, R9C3 |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Door frames: material, plumb and finish | OK | β |
Frame free of cracks and open internal joints | OK | Door frame crack observed in main door. Already discussed in Living area section. |
No gap between frame, beading/architrave and wall | OK | Master bedroom door alignment issue between door and frame. Already discussed in Bedroom1 /Master bedroom |
Frame, beading and architrave undamaged | OK | β |
No gap between frame and finished floor | OK | Master bedroom door has an uneven gap. |
Lock receiving (strike) plate fixed | OK | β |
Door shutter perimeter gap | OK | β |
Shutter free from chips, scratches and cracks | OK | β |
Hinges, handles, bolts and stoppers | OK | β |
Hinge screws complete and rust-free | OK | β |
Lock, handle and tower bolt operate smoothly | OK | Auto locking not working as expected in bedroom. Highlighted in all bedroom sections. |
Doors operate easily and noiselessly | OK | β |
Shutter warping, swelling or delamination | OK | β |
Veneer/laminate polish finish | OK | β |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Window frame external sealant | OK | β |
Frame corner joints free of gaps | OK | β |
Sliding rollers, track and locking | OK | β |
Sealing felt (brush pile) fitted in the frame | OK | β |
Drain (weep) holes in the bottom track | OK | β |
Sliding stopper and hook lock on every shutter | OK | β |
Handle fitted and lock operating smoothly | OK | β |
Shutter free from breakage, scratches or cracks | OK | β |
Glass thickness, beading and scratches | OK | β |
Rubber glazing gasket fixed properly | OK | β |
Glass cleaned of cement, paint and stickers | OK | β |
Mosquito mesh shutters, fit and damage | OK | Not Applicable as its not installed. |
External sill slope and drip | OK | β |
Rain water ingress test | OK | Not inspected. |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Distribution board labelling and MCBs | Monitor | MCB labelling has to be done. |
Circuit diagram provided at the flat DB | OK | β |
MCB ratings and circuit separation | OK | β |
Earthing and RCD/RCCB function | OK | β |
Earth resistance measurement | OK | β |
RCCB/ELCB trip test | OK | β |
Line-neutral polarity at sockets | OK | β |
Socket and switch count per room | OK | β |
Every switch, regulator and dimmer | Recommended to fix | Hall Wall 3 wall point is not working. |
Switch and [redacted]r plates fixed properly | OK | No issues observed |
Switch plates aligned horizontally | OK | No issues observed |
Fan regulator fitted on the switch plate | OK | No issues observed |
Gaps and mould around the DB and switch boxes | OK | No issues observed |
Dummy/blank plates on unused boxes | OK | β |
Concealed wiring, conduit and junction boxes | OK | β |
Light fixtures, fans and fixing | OK | Not applicable |
Surge protection device at the DB | OK | No issues observed |
Inverter/UPS and DG backup circuit | OK | β |
BESCOM meter and sanctioned load | OK | Not inspected |
TV, telephone and internet cabling | OK | β |
Fire safety and emergency egress | OK | Not inspected |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Plumbing pressure test evidence | OK | Water pressure is normal |
Water source: Cauvery/BWSSB and borewell | OK | Not inspected |
Water quality: TDS, hardness and odour | Monitor | Hard water observed. TDS over 500. |
Overhead tank, level indicator and access | OK | Not inspected |
Underground sump capacity and [redacted]r | OK | Not Inspected |
Individual water meter | OK | Not Inspected |
Booster/hydro-pneumatic pump operation | OK | Not inspected |
Main and zone shutoff valves | OK | As per standard specifications |
Hot water line insulation and routing | OK | No issues observed |
Drainage flow and standing water | Monitor | Found issues in bathrooms and balcony |
Sewage connection to STP or BWSSB main | OK | Not Inspected |
Rainwater harvesting system | OK | Not Inspected |
Solar water heater provision | OK | Not Inspected |
Concealed pipe leak scan | OK | No issues observed |
| Checkpoint | Status | Inspector Comment |
|---|---|---|
Crack width classification | OK | Two cosmetic cracks observed. Discussed in previous sections. |
Beam-column junction and honeycombing | OK | No issues observed |
Slab soffit deflection or sagging | OK | No issues observed |
Cracks at lintel and sill level | OK | No issues observed |
Plaster hollowness by tapping | OK | No issues observed |
Floor flatness under a straightedge | OK | No issues observed |
Tile hollow sound and lippage | OK | Tile hollows found. Discussed in other sections above. |
Wall moisture meter readings | OK | No issues observed |
Ceiling water stains and efflorescence | OK | No issues observed |
Seepage on walls shared with neighbours | OK | Not applicable. Couldn't check the seepage from floor above. |
External wall rain penetration | OK | Not applicable - But not plaster cracks found. |
Wet area pond test | OK | Not applicable |
Sunk slab filling and waterproofing | OK | Not applicable |
Terrace waterproofing above the unit | OK | Not applicable |
Thermal imaging scan | OK | No dampness or leakage observed via thermal scans. |
Area measurement | Monitor | Very very minute area measurement difference. So all good here. |
Yours goes further than this one
This is one home's report β and a trimmed one, since anonymising it stripped things your copy keeps. Yours is written as we walk your property: every room in your layout assessed on its own, only the checkpoints that apply to it, each defect photographed where we found it. It arrives with a plain-English summary of what the findings mean, a repair cost estimate, and β where the defects warrant it β a RERA rectification notice ready to send your builder. 200+ checkpoints, thermal imaging included, within 24 hours of the visit.
Β© 2026 HomeGyan Property Inspections. All rights reserved. This sample report, its layout, findings and photographs are the property of HomeGyan Property Inspections and are published for prospective customers to read. Reproduction or republication, in whole or in part, without written permission is prohibited.